General specifications – Rockwell Automation 1732D-XXXX PointBlock 16 dc Input Module Installation Instructions User Manual

Page 18

Advertising
background image

18 DeviceNet 1732 ArmorBlock 16-Point I/O, Series A

Publication 1732D-IN002B-EN-E - January 2013

Isolation voltage

50V (continuous), Basic Insulation Type, Outputs and Output
Power to Network

No isolation between individual Outputs or between Outputs
and Output power

Type tested at 707V DC for 60 s

Surge current per output, max

1.2 A for 10 ms, repeatable every 2 s (1732D-16CFGM12y)

4.8 A for 10 ms, repeatable every 2 s (1732D-OB16M12y)

Pilot duty rating

Not rated

General Specifications

Attribute

Value

Voltage, auxiliary power, max

30V DC

Voltage, auxiliary power, min

12V DC

Voltage, DeviceNet power, max

25V DC

Voltage, DeviceNet power, min

11V DC

Current, auxiliary power input, max

900 mA

Current, auxiliary power, max

8 A

Current, sensor source, per input, max

50 mA

Current, sensor source, per module, max 800 mA

Communication rate

125 Kbps @ 500 m (1640 ft) for thick cable,

flat media length 375 m (1230 ft)

250 Kbps @ 200 m (600 ft) for thick cable,

flat media length 150 m (492 ft)

500 Kbps @ 100 m (330 ft) for thick cable,

flat media length 75 m (246 ft)

DeviceNet current

100 mA (75 mA for 1732E-IB16M12y)

Indicators

1 green/red module status

1 green/red network status

1 green auxiliary power

16 yellow input/output status

Enclosure type rating

Meets IP65/66/67/69K (when marked), and NEMA 4X/6P with
recepticle dust caps or cable termination

DeviceNet 1732 ArmorBlock 16-Point I/O, Series A - 1732D-OB16M12M12,
1732D-OB16M12MINI 1732D-16CFGM12M12, 1732D-16CFGM12MINI

Attribute

Value

Advertising