Input specifications – Rockwell Automation 1746-NI16V SLC 500 Analog I/O Modules User Manual

Page 17

Advertising
background image

SLC 500™ Analog Input Modules 17

Publication 1746-IN001B-US-P

Input Specifications

Description

Specification

Type of Input (Selectable)

NI16V

±10V dc, 1 to 5V, 0 to 5V, or 0 to 10V

NI16I

±20 mA, 4 to 20 mA, 0 to 1 mA, 0 to 20 mA

Type of Data (Selectable)

Engineering Units (1 mV/step or 1 µA/step)

Scaled-for-PID (0 to +16,383 range)

Proportional Counts (-32,768 to +32,767 range)

Proportional Counts (User Defined Range, Class 3 only)

1746-NI4 Data Format

Input Impedance

NI16V

20 M

NI16I

249

Maximum Voltage Input
without damage

NI16V

±30V between any two signal terminals

Maximum Voltage Input
without damage

NI16I

±8V between any two signal terminals

Current Input (maximum)

±30 mA (Between analog com and any input terminal)

Time to Detect Open Circuit

Less Than 5 seconds

Module Update Time

(1)

(1)

Depends on filter selected. Refer to the 1746-NI16 User Manual, publication 1746-UM001A-US-P.

Input Resolution

NI16V

312 µV

(2)

(2)

Depends on data mode: Engineering Units or Proportional Counts

.

NI16I

640 nA

Display Resolution

1 mV or 1 µA

Module Error Over Full
Temperature Range
(0°C to 60°C, 32°F to 140°F)

NI16V

Voltage input types (±10V dc, 1 to 5V dc, 0 to 5V dc, 0 to
10V dc): ±0.1%

NI16I

Current input types (0 to 20 mA, 4 to 20 mA, 0 to 1mA,
±20 mA): ±0.3%

Input Offset Drift with
Temperature

NI16V

90 µV/°C

NI16I

360 nA/°C

Gain Drift with Temperature

NI16V

15 ppm/°C

NI16I

20 ppm/°C

Calibrated Accuracy at 25°C

NI16V

Better than 0.05% of range

NI16I

Better than 0.15% of range