Electrostatic damage, 1746-ni16 power requirements – Rockwell Automation 1746-NI16V SLC 500 Analog I/O Modules User Manual

Page 5

Advertising
background image

SLC 500™ Analog Input Modules 5

Publication 1746-IN001B-US-P

Electrostatic Damage

Electrostatic discharge can damage semiconductor devices inside this module if you
touch backplane connector pins. Guard against electrostatic damage by observing
the following precautions.

1746-NI16 Power Requirements

The 1746-NI16 module receives its power through the SLC 500 chassis backplane
from the fixed or modular +5V dc/+24V dc chassis power supply. The +5V dc
backplane supply powers the SLC circuitry and the +24V dc backplane supply
powers the module analog circuitry. The maximum current drawn by the module is
shown in the table below.

When you are using a modular system configuration, add the values shown in the
table above to the requirements of all other modules in the SLC chassis to prevent
overloading the chassis power supply.

!

ATTENTION

Electrostatic discharge can degrade performance or cause
permanent damage. Handle the module as stated below.

• Wear an approved wrist strap grounding device when

handling the module.

• Touch a grounded object to rid yourself of electrostatic charge

before handling the module.

• Handle the module from the front, away from the backplane

connector. Do not touch backplane connector pins.

• Keep the module in its static-shield bag when not in use, or

during shipment.

5V dc Amps

24V dc Amps

125 mA

75 mA

@JO#VTQQE

@JO#VTQQE

".

".

Advertising