Mold Pressure Module

Publication 1746-5.13 July 1998

Summary data notes

Single-word

summary values are stored with bytes reversed. You must use

the Swap instruction to convert them to integer format.

Double-word

summary values are stored as integer pairs, with the low-

word value stored in the lower address of the pair, high-word value in upper.

12. Specifications

Description:

Value:

electrical

backplane current
backplane power
number of input channels
A/D conversion
common-mode rejection
dynamic response

0.3A @ 5V dc
1.5W
2
12-bit successive approximation
115 do @ 500 gain
200K Hz @ 500 gain

sensor inputs

input types lo-level

input types hi-level
gain settings
sensor excitation voltage
sensor excitation current
isolation from backplane

2, 6, and 9 mV/V strain gage
4-20mA self-powered
0-10V dc
1, 100, 250, 450
10.000V dc ±0.002V dc
35mA per channel
1500V rms

mechanical

module ID
number of LED indicators
cable for channels
cable for DartNets

12935
4 (alarm condition and module status)
Belden 8102
Belden 9462

temperature

operating
storage

0° to 60° C

(32 to 140° F)

-40° to 85° C

(-40 to 185° F)

relative humidity

5% to 95% noncondensing

agency certification

1

(when product or packaging is marked)

1.

CSA certification - Class I Division 2, Group A, B, C, D or nonhazardous locations
FM approved - Class I, Division 2, Group A, B, C, D or nonhazardous locations

Class I Division 2 Hazardous

marked for all applicable directives