1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 17

Publication 1732E-IN005B-EN-E - September 2012

Specifications

I/O status

Off

The input channel is inactive, can be calibrated.

Flashing Green

Channel is calibrating.

Green

Normal operation, inputs being scanned.

Flashing Yellow

Thermistor fault.

Flashing Red

Fault. Overrange, underrange, or process alarm is present.

Red

No power is detected.

IMPORTANT

The Module Status LED indicator will flash red and green for a maximum
30 s while the module completes its POST (Power-On Self Test).

General Specifications

Attributes

Value

Voltage, power, max

30V DC

Voltage, power, min

12V DC

Module power

12…30V DC @ 300 mA

Power consumption

3 W @ 24V DC, typical

3.5 W, max (module unloaded)

Isolation voltage

50V (continuous), Basic Insulation Type

Type tested @ 707V DC for 60 s

Communication rate

EtherNet/IP

10/100 Mbps

Full or half-duplex

100 meter per segment