8 1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules

Publication 1732E-IN005B-EN-E - September 2012

If DHCP is not enabled, the I/O block uses the IP address (along with other TCP
configurable parameters) stored in nonvolatile memory.

Network Address Switch value 001

The module IP address cannot be the same as the gateway address. If the address switches
are set to 001, the module IP address becomes 192.168.1.1, which is the same as the default
gateway address. In this case, the module gateway address will be set to 0.0.0.0.

Default Factory Configuration

The switch value 888 resets the module to default factory configuration on power up. The
module will not operate properly when powered up with this setting. The switches must be
set to a different (and valid) value and then power cycled after a reset.

While in reset state, the module LED flashes red and the network LED goes off.

Mount the Module

Two sets of mounting holes are used to mount the module directly to a panel or machine.
Mounting holes accommodate #6 (M3) pan head screws. The torque specification is
0.68 Nm (6 lb-in.).

Product Dimensions

Refer to the mounting dimensions illustration to help you mount the module.