Rockwell Automation 1732E-IR4IM12R ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input User Manual

Page 21

Advertising
background image

1732E ArmorBlock Dual-Port EtherNet/IP 4-Point Thermocouple and RTD Input Modules 21

Publication 1732E-IN005B-EN-E - September 2012

Input range

RTD type

Temperature

Range (°C)

Voltage Range

100

 Pt 385

0…390.48

-200…850 °C

0…156.25 mV

200

 Pt 385

0…781

-200…850 °C

0…312.5 mV

100

 Pt 3916

0…337.03

-200…630 °C

0…156.25 mV

200

 Pt 3916

0…674.06

-200…630 °C

0…312.5 mV

10

 Cu 427

0…19.116

-320…500 °C

0…19.53 mV

120

 Ni 672

0…445.10

-70…445 °C

0…156.25 mV

100

 Ni 618

0…198.88

-60…180 °C

0…78.125 mV

120

 Ni 618

0…238.65

-90…140 °C

0…78.125mV

Accuracy

0.1% Full Scale @ 25 °C (77 °F)

Accuracy drift with
temperature

30 ppm % Full Scale /°C @ 25 °C (77 °F)

Calibration

Factory calibrated. Calibration is also supported through RSLogix 5000.

Sample Rate
Filters

(1)

50 Hz

60 Hz

250 Hz

500 Hz

Common Mode
Rejection Ratio

120 dB @ 50/60 Hz

Normal Mode
Rejection Ratio

100 dB @ 50/60 Hz

(1)

Sample rate filter selectable on a module basis only.

Input Specifications – 1732E-IR4IM12R