Chapter 2

Wiring and Installation

2–3

The DIO Link must be terminated at each end with an 82 Ohm 1/2 watt
resistor. The resistor is connected across Line 1 and Line 2. In addition,
Chassis Grounding Method One is illustrated below.

Clear

Shield

Blue

82

Terminating

Resistor

SN

SCANNER

Line 2

Shield

Line 1

Chassis Ground

Clear

Shield

Blue

Terminating
Resistor

82

Terminating

Resistor

A

2

COM

B

1

SHD

A

2

COM

B

1

SHD

A

2

COM

B

1

SHD

DIO Clear (line 2)

DIO Blue (line 1)

DIO / DH–485 shield

A

2

COM

B

1

SHD

DIO Clear (line 2)

DIO Blue (line 1)

DIO / DH–485 shield

Chassis Grounding

Method 1

1

Because the DIO / DH–485 shields are tied together at each block, you should only connect the shield to chassis
ground in one place. If you choose to ground the shields using Chassis Grounding Method 1 (shown here), do
not use Chassis Grounding Method 2 (shown on page 2–5).

1

DIO Connector for the I/O block

DIO Connector for the I/O block