Control word configuration information, 30 i/o block configuration output image example – Rockwell Automation 1747-DSN DISTRIBUTED I/O SCANNER User Manual

Page 27

Advertising
background image

Input File

Control Word, Word 0

O:e.0

O:e.1

O:e.15

O:e.16

I/O block 1 (Output, Word 1)

I/O block 15 (Output Word 15)

Reserved, Word 16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

Bit Number (decimal)

e = slot number of the SLC rack containing the scanner

Bits 6 and 7are only available to I/O

blocks with 8 outputs

Configuration Data Valid

bit 10

Disable Outputs

bit 9

Number of I/O

blocks bits 0 – 4

Reserved

The output word for each I/O block is placed in the word corresponding to the
I/O block address. The bits of each output word correspond to the outputs on
the I/O block. For example, bit 5 of output word 31 controls output 5 of I/O
block 31.

Control Word Configuration Information

1

1

2

2

00000 configures the scanner for 7 I/O blocks

Scanner detects rising edge

O:e.31

I/O block 31 (Output Word 31)

Output bits

Chapter 3

Configuration and Programming

3–9

Configuration Data Valid Bit – Bit 10 of the Control Word (word 0) must
be set after bits 0 –4 (Number of I/O blocks) are valid. When this bit is first
set to 1 (from run mode), bits 0 – 4 are used to configure the scanner with the
number of I/O blocks connected to the scanner.

Important: This bit should not be reset to 0 during program execution.

After this bit is set, further transitions of bits 0 – 4 (Number of I/O blocks)
are ignored.

30 I/O Block Configuration Output Image Example

Configurable Item

Values

Result

Number of I/O Blocks

00001 to 11110

1 – 30 I/O blocks

Disable Outputs

0
1

Outputs enabled

Outputs disabled

Configuration Data Valid

0
1

Invalid

Valid