Chapter 3

Configuration and Programming

3–8

30 I/O Block Configuration Output Image

The 30 I/O block configuration output image consists of 32 words (one
control word, one reserved word, and 30 output words). Each output word
has a corresponding I/O block address. For example, the output data for I/O
block 31 (there is no I/O block 16) is located in output word 31. In addition,
the bits of each output word correspond to the outputs on the I/O block. For
example,

For I/O blocks with 6 outputs, bits 0 – 5 are valid.

For I/O blocks with 8 outputs, bits 0 – 7 are valid.

Control Word (Word 0)

The Control Word controls the following three functions:

Number of I/O blocks – bits 0 – 4 configure the scanner for the number of
I/O blocks physically connected to the scanner. I/O blocks must be
numbered consecutively starting with one. They do not have to be wired in a
contiguous order.

The maximum number of I/O blocks you can configure is 30. Any
number larger than 30 causes configuration error

xx62

in the SLC 5/02

and

xx58

in the SLC 5/01

.

When bits 0 – 4 equal 0, the system defaults to 30 I/O blocks, the
maximum number of I/O blocks this configuration allows.

Configure the scanner for the number of I/O blocks connected. If you
configure it for more I/O blocks than what you have connected, you will
waste throughput time trying to scan I/O blocks that do not exist on the
link. If you configure it for fewer I/O blocks than you have connected,
the scanner will not communicate with I/O blocks which have higher
address numbers than the number of configured I/O blocks.

Disable Outputs – When bit 9 is set and the SLC processor is in run mode,
the scanner disables all outputs on all I/O blocks. Whether the disabled
outputs are reset to 0 or held in their last state depends on the Hold Last State
dip switch setting (located on each I/O block).

If bit 9 is set and the Hold Last State function is disabled, the outputs will
be reset to 0.

If bit 9 is set and the Hold Last State function is enabled, the outputs are
held in their last state.

Important: The Disable Outputs bit is constantly monitored by the scanner

when the SLC processor is in run mode.