Error codes – Rockwell Automation 1747-DSN DISTRIBUTED I/O SCANNER User Manual
Page 38
Chapter 4
Operation and Troubleshooting
4–8
Error codes are reported in word 6 of the SLC processor status file. The
format of the status word and applicable error codes are shown below:
Slot Number
Error Code
01H to 1EH
.
The table below lists and explains the possible errors that you may encounter
using an SLC 5/01 or 5/02 processor with the DIO scanner.
If you are using an
the following error
message(s)
indicate(s)
SLC 5/01 processor
58H
configuration for an invalid number
of I/O blocks or scanner hardware
problem or duplicate scanner.
SLC 5/02 processor
6BH
duplicate scanner
62H
configuration for an invalid number
of blocks
68, 69, 6A, 6C, 6D, 6E, 6FH
scanner hardware problem
For a complete description of the error codes, refer to the user’s manual
provided with your programming device.
Error Codes