Error codes – Rockwell Automation 1747-DSN DISTRIBUTED I/O SCANNER User Manual

Page 38

Advertising
background image

Chapter 4

Operation and Troubleshooting

4–8

Error codes are reported in word 6 of the SLC processor status file. The
format of the status word and applicable error codes are shown below:

Slot Number

Error Code

01H to 1EH

.

The table below lists and explains the possible errors that you may encounter
using an SLC 5/01 or 5/02 processor with the DIO scanner.

If you are using an

the following error
message(s)

indicate(s)

SLC 5/01 processor

58H

configuration for an invalid number
of I/O blocks or scanner hardware
problem or duplicate scanner.

SLC 5/02 processor

6BH

duplicate scanner

62H

configuration for an invalid number
of blocks

68, 69, 6A, 6C, 6D, 6E, 6FH

scanner hardware problem

For a complete description of the error codes, refer to the user’s manual
provided with your programming device.

Error Codes