10 MicroLogix 1762-OV32T Solid State 24V DC Sink Output Module

Publication 1762-IN021B-EN-P - July 2013

Panel Mounting

Use the dimensional template shown below to mount the module. The preferred mounting
method is to use two M4 (#8) panhead screws per module. M3.5 (#6) panhead screws may also
be used, but a washer may be needed to ensure a good mechanical contact. Mounting screws are
required on every module.

System Assembly

The expansion I/O module is attached to the controller or another I/O module by means of a
flat ribbon cable after mounting as shown below.

TIP

Use the pull loop on the connector to disconnect modules. Do not pull on the
ribbon cable.

90
(3.54)

100.06
(3.939)

40.4
(1.59)

40.4
(1.59)

14.2
(0.568)

MicroLogix

1100/1200/1400

1762 I/O

1762 I/O

1762 I/O

95 (3.74)

44914

For more than two I/O modules: measure (number of modules - 1) x 40 mm (1.59 in.)

NOTE: All dimensions are in mm (in.). Hole spacing tolerance: ±0.4 mm (0.016 in.).

44569

Bus connector covers

1762 expansion
bus connector
cover