MicroLogix 1762-OV32T Solid State 24V DC Sink Output Module 17

Publication 1762-IN021B-EN-P - July 2013

Specifications

General Specifications

Attribute

Value

Number of outputs

32

Dimensions, HxWxD

90 x 40.4 x 87 mm (3.54 x 1.59 x 3.43 in.)

Shipping weight, approx.

200 g (7.05 oz)

Bus current draw, max

175 mA @ 5V DC
0 mA @ 24V DC

Heat dissipation

2.7 W @ 26.4 V DC

Wire size

22, 24, 26 AWG solid or stranded copper wire rated @ 90 °C (194 °F)

Wiring category

(1)

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 - on signal ports

Pilot duty rating

Not rated

Enclosure type rating

IP20

North American temp code

T3C

Output Specifications

Attribute

Value

Isolated groups

Group 1: Outputs 0...15
Group 2: Outputs 16...31 (internally connected to common)

Output group to backplane isolation

Verified by one of the following dielectric tests:
1200V AC for 2 s or 1697V DC for 2 s.
75V DC working voltage (IEC Class 2 reinforced insulation)

Vendor I.D. code

1

Product type code

7

Product code

102

Voltage category

24V DC sink

Operating voltage range

10.2...26.4V DC

Signal delay, max resistive load

Turn-on = 0.5 ms
Turn-off = 4.0 ms

On-state current, min

1.0 mA

Off-state leakage current, max

0.1 mA @ 26.4V DC

On-state voltage drop, max

0.3V DC @ 0.5 A

Continuous current, per point, max

0.5A @ 60 °C (140 °F)