18 MicroLogix 1762-OV32T Solid State 24V DC Sink Output Module

Publication 1762-IN021B-EN-P - July 2013

Continuous current, per common, max

2.0 A @ 60 °C (140 °F)

Continuous current, per module, max

4.0 A @ 60 °C (140 °F)

Surge current, max

2.0 A - Repeatable every 2 s @ 60°C (140°F) for 10 ms

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20... 60 °C (-4...140 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40…85 °C (-40…185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10... 500 Hz

Altitude, operating max

2000 m (6562 ft)

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Panel mount - 50 g
DIN mount - 40 g

Emissions

CISPR 11
Group 1, Class A

ESD immunity

IEC 61000-4-2:
4 kV contact discharges
8 kV air discharges
4 kV indirect

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2700 MHz

Output Specifications