14 POINT I/O Module with 8 Configurable 24V DC Points
Publication
1734-IN038A-EN-P - October 2008
Wiring Diagram
Channel
Terminal Number
I/O
Common
Voltage
0
0
External
(1)
(1)
Common connections require an external connection, such as a 1734-CTM module.
External
(2)
(2)
Supply Voltage Connections require an external connection such as a 1734-VTM module.
1
1
2
2
3
3
4
4
5
5
6
6
7
7
10/28.8 V DC is supplied through the internal power bus.
Prox
I/O 0
Load
Prox
Prox
Prox
Load
Load
Load
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
V C
C
If a connection to Common or the Supply Voltage is required for two- or three-wire
devices, then a 1734-CTM or 1734-VTM can be used.
Each I/O point is either Input or Output.