Interpret the indicators – Rockwell Automation 1734-8CFG POINT I/O Module with 8 Configurable 24V DC Points IN User Manual

Page 17

Advertising
background image

POINT I/O Module with 8 Configurable 24V DC Points 17

Publication

1734-IN038A-EN-P - October 2008

Interpret the Indicators

See the figure and table that show how to interpret indicators.

Indicator

State

Description

Module
status

Off

No power applied to device.

Green

Device operating normally.

Flashing green

Device needs commissioning due to configuration
missing, incomplete or incorrect.

Flashing red

Recoverable fault.

Red

Unrecoverable fault may require device replacement.

Flashing red/green

Device is in self-test.

1

3

0

2

Module

Status

Network

Status

24Vdc

SINK IN

SOURCE OUT

1734-8CFG

1

3

0

2

5

7

4

6

NODE:

NODE:

Module Status

Network Status

44688

Status of I/O 0

Status of I/O 1

Status of I/O 2

Status of I/O 3

Status of I/O 4

Status of I/O 5

Status of I/O 6

Status of I/O 7