18 POINT I/O 24V dc Digital Diagnostics Input Module

Publication

1734-IN029A-EN-E - January 2007

Configure the Module

Read this section for information about how to communicate with
your module.

I/O messages are sent to (consumed) and received from (produced)
the POINT I/O modules. These messages are mapped into the
processor’s or scanner’s memory. This POINT I/O input module
produces 1 or 2 bytes of input data based on which produced
assembly is selected. The default setup is 2 bytes. It does not
consume I/O data (scanner Tx).

Default Data Map - Produced Assembly Instance 101

Message Size: 2 Bytes

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault
3

Fault
2

Fault
1

Fault
0

Input
3

Input
2

Input
1

Input
0

Produce 1 (Rx)

SC 3

SC 2

SC 1

SC 0

OW 3

OW 2

OW 1

OW 0

Consume (Tx)

No consumed data

Where: OW = open wire, SC = short circuit, fault = open wire or short circuit.

Data Map - Produced Assembly Instance 23

Message Size: 1 Byte

7

6

5

4

3

2

1

0

Produce 0 (Rx)

Fault
3

Fault
2

Fault
1

Fault
0

Input
3

Input
2

Input
1

Input
0

Consume (Tx)

No consumed data

Where: Fault = open wire or short circuit.