Specifications – Rockwell Automation 1734-IB4D POINT I/O 24V dc 4-Channel Discrete Input Module Installation Instructions User Manual

Page 24

Advertising
background image

24 POINT I/O 24V dc Digital Diagnostics Input Module

Publication

1734-IN029A-EN-E - January 2007

Specifications

POINT I/O 24V dc 4-channel Digital Diagnostics Input Module - 1734-IB4D

Attribute

Value

Module Location

1734-TB, 1734-TBS, 1734-TOP, and 1734-TOPS bases

POINTBus Current

50 mA max @ 5V dc

Power Dissipation

0.6 W max @ 28.8V dc

Thermal Dissipation

1.9 BTU/hr max @ 28.8V dc

Isolation Voltage

50Vdc (continuous), Reinforced Insulation Type
Tested at 1000 V dc for 60 s, field-side to system

Field Power Bus
Supply Voltage
Voltage Range

24V dc nom
10…28.8V dc

Dimensions HxWxL, approx.

56 x 12 x 75.5 mm
2.2 x 0.47 x 2.97 in.

Terminal Base Screw Torque

0.8 Nm (7 lb-in)

Keyswitch Position

1

Reverse Polarity Protection

Yes

On-state Voltage (Von), Min

11V dc

On-state Voltage (Von), Max

28.8V dc (Vmax)

On-state Current (Ion), Min

2.0 mA

On-state Current (Ion), Max

15.0 mA (Imax)

Off-state Voltage (Voff), Min

-3V dc

Off-state Voltage (Voff), Max

5V dc

Off-state Current (Ioff), Min

1.5 mA

Input Filter

Each input independently settable in 1 us intervals
(rounded to nearest 333 us).
Default value is 1000 us.

Off to On Filter, Min

0 us

Advertising