Rockwell Automation 1734-IB4D POINT I/O 24V dc 4-Channel Discrete Input Module Installation Instructions User Manual

Page 19

Advertising
background image

POINT I/O 24V dc Digital Diagnostics Input Module 19

Publication

1734-IN029A-EN-E - January 2007

Default Data Map - Configuration Assembly Instance 103

Message Size: 18 Bytes

7

6

5

4

3

2

1

0

Consume 0

Input 0 Off to On Filter Byte 0

Consume 1

Input 0 Off to On Filter Byte 1

Consume 2

Input 0 On to Off Filter Byte 0

Consume 3

Input 0 On to Off Filter Byte 1

Consume 4

Input 1 Off to On Filter Byte 0

Consume 5

Input 1 Off to On Filter Byte 1

Consume 6

Input 1 On to Off Filter Byte 0

Consume 7

Input 1 On to Off Filter Byte 1

Consume 8

Input 2 Off to On Filter Byte 0

Consume 9

Input 2 Off to On Filter Byte 1

Consume 10

Input 2 On to Off Filter Byte 0

Consume 11

Input 2 On to Off Filter Byte 1

Consume 12

Input 3 Off to On Filter Byte 0

Consume 13

Input 3 Off to On Filter Byte 1

Consume 14

Input 3 On to Off Filter Byte 0

Consume 15

Input 3 On to Off Filter Byte 1

Consume 16

Autobaud
Disable

Enable
OW3

Enable
OW2

Enable
OW1

Enable
OW0

Consume 17

Produced Assembly Instance

Produce (Tx)

No produced data

Where: OW = open wire.