POINT I/O 24V dc Digital Diagnostics Input Module 25

Publication

1734-IN029A-EN-E - January 2007

Off to On Filter, Max

65,535 us

On to Off Filter, Min

0 us

Off to On Filter, Max

65 535 us

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20…55 °C (-4…131 °F)

Temperature, storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock):
-40…85°C (-40…185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Shock
Operating
Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock)
30 g peak acceleration
50 g peak acceleration

Vibration

IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10…500 Hz

ESD Immunity

IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80%AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

EFT/B Immunity

IEC 61000-4-4: ±4 kV at 5 kHz on signal ports

POINT I/O 24V dc 4-channel Digital Diagnostics Input Module - 1734-IB4D

Attribute

Value

Advertising