DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A 11

Publication

1732D-IN011A-EN-E - April 2009

Communicate with Your Module

This module’s I/O is exchanged with the master through a cyclic, polled, or
change-of-state connection.
Cyclic - allows configuration of the block as an I/O client. The block will
produce and consume its I/O cyclically at the rate configured.
Polled - a master initiates communication by sending its polled I/O message
to the module. The module consumes the message, updates outputs, and
produces a response. The response has input data.
Change-of-State - productions occur when an input changes or a fault
condition occurs. If no input or fault condition change occurs within the
expected packet rate, a heartbeat production occurs. This heartbeat
production tells the scanner module that the I/O module is alive and ready to
communicate. Consumption occurs when data changes and the master
produces new output data to the I/O block.
Refer to the Module Data Definitions table for more information.

1732D-8X81212HD Data Definitions

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Produce 0

I7

I6

I5

I4

I3

I2

I1

I0

Produce 1

In Short

Out Short

Consume 0

O7

O6

O5

O4

O3

O2

O1

O0

Where:

I=Input Data; 0=Off, 1=On

In Short 0=Working, 1=Sensor Source Voltage Fault

Out Short 0=Working, 1=Output Fault (Short)

O=Output Data; 0=Off, 1=On