Rockwell Automation 1732D-8X81212HD DNet ArmorBlock Network and Auxiliary Powered Module, Series A, IN User Manual

Page 13

Advertising
background image

DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A 13

Publication

1732D-IN011A-EN-E - April 2009

Network Status

Status

Description

Recommended action

Off

Device is not online.

Wait until the device has
completed the dup_MAC_id test
or apply power to the device.

Green

Device is operating normally and is
online with connections in the
established state. As a Group 2
module, it means that the module is
allocated to a master.

None.

Flashing
Green

Device is online with no connections
in the established state.

Establish connections to other
nodes. As a group 2 module,
allocate the module to a master.

Red

Critical link failure – failed
communication module.

Check your configuration and cycle
power.

Flashing Red

Recoverable fault – an I/O
connection has timed out.

Cycle power to the module.

Advertising