Rockwell Automation 1732D-8X81212HD DNet ArmorBlock Network and Auxiliary Powered Module, Series A, IN User Manual
Page 13
DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A 13
Publication
1732D-IN011A-EN-E - April 2009
Network Status
Status
Description
Recommended action
Off
Device is not online.
Wait until the device has
completed the dup_MAC_id test
or apply power to the device.
Green
Device is operating normally and is
online with connections in the
established state. As a Group 2
module, it means that the module is
allocated to a master.
None.
Flashing
Green
Device is online with no connections
in the established state.
Establish connections to other
nodes. As a group 2 module,
allocate the module to a master.
Red
Critical link failure – failed
communication module.
Check your configuration and cycle
power.
Flashing Red
Recoverable fault – an I/O
connection has timed out.
Cycle power to the module.