6 DeviceNet ArmorBlock Network and Auxiliary Powered Module, Series A

Publication

1732D-IN011A-EN-E - April 2009

To reset the node address:

1. Rotate the switches using a small blade screwdriver.

2. Line up the small black dot on the switch with the number setting you

wish to use.

3. Cycle power.

The rotary switches are read periodically. If the switches have been changed
since the last time they were read and they no longer match the online address,
a minor fault occurs, which is indicated by a flashing red MOD LED.
Settings of 64 through 99 cause the module to use the last valid node address
stored internally. For example, the last setting internally was 40. If a change is
made to 68, and then you power up, the address defaults to 40.
The module is equipped with AutoBaud detect. AutoBaud lets the module
read the settings already in use on your DeviceNet network and automatically
adjusts to those settings.

Mount the Module

Two sets of mounting holes are used to mount the module directly to a panel
or machine. Mounting holes accommodate #6 (M3) pan head screws. The
torque specification is 0.64 Nm (6 in-lb).

Example shows
default node
address set at 63.