14 ArmorPoint EtherNet/IP Adapter, Series A

General Specifications (continued)

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz

10V/m with 200Hz 50% Pulse 100%AM at 900Mhz

10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz

EFT/B Immunity

IEC 61000-4-4:

±4kV at 5kHz on power ports

±2kV at 5kHz on communication ports

Surge Transient Immunity

IEC 61000-4-5:

±1kV line-line(DM) and ±2kV line-earth(CM) on power ports

±2kV line-earth(CM) on unshielded communications port (tested as balanced circuits)

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz

Emissions

CSPR 11:

Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque

#8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel

Wiring Category

1

1 - on power ports

1 - on communications ports

Weight

Imperial (Metric)

0.80 lb. (0.36 kg)

Certifications:

2

(when product is marked)

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada

CE

European Union 89/336/EEC EMC Directive, compliant with:

EN 61000-6-4; Industrial Emissions

EN 50082-2; Industrial Immunity

EN 61326; Meas./Control/Lab., Industrial Requirements

EN 61000-6-2; Industrial Immunity

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

EtherNet/IP

ODVA conformance tested to EhterNet/IP specifications

1.

Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, Industrial Automation Wiring

and Grounding Guidelines".

2.

See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.