Publication 1738-IN017B-EN-E - March 2005

ArmorPoint EtherNet/IP Adapter, Series A 5

Establish I/O Connections

When you power up a ArmorPoint I/O system and establish I/O
connections, the outputs transition to the Idle state, applying Idle state
data before going to RUN mode. This occurs even when the controller
making the connection is already in RUN mode.

Configure Autobaud

The adapter cannot reconfigure an I/O module that you previously
configured to operate at a fixed baud rate. When you reuse a
ArmorPoint I/O module from another ArmorPoint I/O system,
configure the module to autobaud before using it with the adapter.

For More Information

Refer to the ArmorPoint I/O EtherNet/IP Adapter Release Notes,
publication 1738-RN002, online at URL
http://literature.rockwellautomation.com.