POINT I/O DeviceNet Adapter 17

Publication

1734-IN026A-EN-P - April 2005

Adapter
Status

Off

No power is applied to device.

Power the adapter.

Green

Device is operating normally.

None

Flashing
Green

Device needs to be
commissioned because
configuration is missing,
incomplete, or incorrect

Check configuration and
recommission the adapter.

Flashing
Red

Recoverable fault is present.

Make sure the adapter does
not need a FLASH update.

Red

Unrecoverable fault may require
device replacement.

Replace the adapter.

Flashing
Red/Green

Device is in self-test.

Wait for self-test to finish.

Network
Status

Off

Device is not online.
- Device is autobauding .
- Device has not completed
dup_MAC_id test.
- Device is not powered.

Check adapter status
indicator to determine if you
need more time to complete
the dup_MAC_id test or if
you need to power the
adapter.

Flashing
Green

Device is online but has no
connections in the established
state.

None

Green

Device is online and has
connections in the established
state.

None

Flashing
Red

One or more I/O connections are
in timed-out states

Determine the cause of the
time-out. You may need to
increase the expected
packet rate.

Red

Critical link failure -
communication device failed.
Device detected error that
prevents it from communicating
on the network.

Make sure the device is
using the correct MAC ID
and baudrate.

Indicator

Indication

Probable Cause

Take This Action