8 point i/o devicenet adapter publication – Rockwell Automation 1734-ADN, ADNX Point I/O DeviceNet Adapter Installation Instructions User Manual

Page 8

Advertising
background image

8 POINT I/O DeviceNet Adapter

Publication

1734-IN026A-EN-P - April 2005

4. Set the node address by pressing the + and - buttons on the

2-position thumbwheel switch.

Valid physical settings range from 00 to 63.

You can also set the node address to some value between
64-99. In this case, you can change the adapter’s node address
via the RSNetWorx for DeviceNet software.

If you use a value between 64-99, at power-up you use the
node address stored in the adapter’s non-volatile memory.

42510

Module
Status

PointBus
Status

ControlNet A
Status

1734-ACNR

ControlNet B
Status

0 2

42510

Network node
address
thumbwheel