Interpret status indicators – Rockwell Automation 1738-AENTR, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapter User Manual

Page 11

Advertising
background image

1738 ArmorPOINT I/O Dual Port EtherNet/IP Adapter 11

Publication 1738-IN030A-EN-P - July 2013

Interpret Status Indicators

Refer to the following diagram and table for information on how to interpret the
status indicators.

ArmorPOINT I/O Dual Port EtherNet/IP Adapter, Series B

Indicator Status for Modules

Indicator

State

Description

Adapter
status

Off

No power applied to device

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Solid green

Device operating normally

Flashing red

Recoverable fault.

Complete firmware update, verify address switches.

Solid red

Unrecoverable fault:
• Self-test failure (checksum failure, RAM test failure at cycle power)
• Firmware fatal error).

Flashing
red/green

Module self-test

Adapter Status indicator
Network Activity indicator
Network Status indicator

System Power indicator
Adapter Power indicator

POINTBus Status

1738-AENTR
Series B

EtherNet I/P

Adapter
Status

Network
Activity

Network
Status

PointBus
Status

System
Power

Adapter
Power

conformance tested

PWR

IP ADDRESS

Link 2
Activity/
Status

Link 1
Activity/
Status

44830

Link 1 Activity/Status
indicator

Link 2 Activity/Status
indicator

Advertising