12 1738 ArmorPOINT I/O Dual Port EtherNet/IP Adapter

Publication 1738-IN030A-EN-P - July 2013

Network
Activity

Off

No link established with Port 1 or Port 2.

Flashing green

Transmit or receive activity present on Port 1 and/or Port 2 @ 100 Mbps.
Transmit or receive activity present on Port 1 and/or Port 2. One port @
100 Mbps and one port @ 10 Mbps.

Solid green

Link established with Port 1 and/or Port 2 @ 100 Mbps.
Link established with Port 1 and Port 2. One port @ 100 Mbps and one
port @ 10 Mbps.

Solid yellow

Link established with Port 1 and/or Port 2 @ 10 Mbps.

Flashing yellow

Transmit or receive activity present on Port 1 and/or Port 2 @ 10 Mbps.

Network
Status

Off

Device not initialized. Device does not have an IP address.

Flashing green

No CIP connections present. Device has an IP address, but no CIP
connections are established.

Solid green

CIP connections present. Device online and has an IP address, and CIP
connections are established.

Flashing red

One or more CIP connections in timed-out state. Check for I/O module
failure and controller operation.

Solid red

Duplicate IP address detected.

Verify IP address setting and correct, as needed.

Flashing
red/green

Module self-test

Link 1 or Link
2 Activity /
Status

Off

No link established.

Solid green

Link established @ 100 Mbps.

Flashing green

Transmit or receive activity present on indicated port

@ 100 Mbps.

Solid yellow

Link established @ 10 Mbps.

Flashing yellow

Transmit or receive activity present on indicated port @ 10 Mbps.

POINTBus
Status

Off

Device is not online.

Device has not completed Dup_MAC_ID test.

Device not powered - check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Firmware (NVS) update in progress.

Solid green

Adapter online with connections established.

Flashing red

Recoverable fault occurred:
• At cycle power, the number of expected modules does not equal the

number of modules present.

• A module is missing.
• Node fault (I/O connection timeout) occurred.

Solid red

Unrecoverable fault occurred - POINTbus is off.

System
power

Off

Not active. Adapter power is off or there is a DC-DC converter problem.

Solid green

System power is on. DC-DC converter output is active (5V).

Adapter
power

Off

Not active. Adapter power is off.

Solid green

Power is on. 24V input is present.

Indicator Status for Modules

Indicator

State

Description