Rockwell Automation 1738-AENTR, Series B ArmorPOINT I/O Dual Port EtherNet/IP Adapter User Manual

Page 16

Advertising
background image

16 1738 ArmorPOINT I/O Dual Port EtherNet/IP Adapter

Publication 1738-IN030A-EN-P - July 2013

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% noncondensing

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10...500 Hz

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

Emissions

CISPR 11:
Class A

ESD immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz

EFT/B immunity

IEC 61000-4-4:
±4 kV @ 2.5 kHz on power ports
±3 kV @ 5 kHz on communications ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on communications ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Environmental Specifications

Attribute

Value

Advertising