Under Data Transfer Parameters, the Status field displays the
current Data Transfer status (started or stopped). If necessary, click
[Start] or [Stopped] to start or stop Data Transfer.

5.

Set the following Data Transfer properties:

Check the Enable Auto Transfer box if you want to have
FactoryTalk Historian ME transfer data automatically for newly
created points.

6.

Click [Save].

The Data Transfer process records performance statistics that
determine the connection reliability. These statistics can be used to
refine the settings in the configuration subsystem.

The Data

Transfer Statistics section of the Data Transfer page contains the
following information:

“FTMS” Points
Available

This represents the total number of points
granted by the license minus the number of
points that are already being transferred to
the FactoryTalk Historian SE Server.

Property Name

Property Description

Maximum Events
Per Transfer

This is the maximum number of events that
can be transferred to FactoryTalk Historian
SE per transfer session. The range is 5,000
to 150,000. The default setting is 50,000.

Property Name

Property Description

Transfer Rate

This is the total number of retrieved events
sent to FactoryTalk Historian SE, divided
by the time spent retrieving events sent to
FactoryTalk Historian SE (in events per
minute).

Property Name

Property Description

Advertising