Configuration errors, Baud rate settings module address switch – Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 11

Advertising
background image

Backup Scanner Module

11

Publication 1747-5.38

Baud Rate Settings

Module Address Switch

The four-position Module Address DIP switch configures the BSN address in the
LSL. The table below shows the address that corresponds to each setting.

Configuration Errors

The module reports the following configuration errors by flashing the fault LED:

• two 1747-BSN modules are configured with the same address

• LSL addresses are not consecutive (addresses must be numbered 0, 1, 2,

etc.)

• last LSL switch is not set in the last module in the link

• last LSL switch is set in a module that is not the last in the link, or

• primary and secondary modules do not have the same configuration settings

(secondary module shows the configuration error)

Position 1

Position 2

Baud Rate

ON

ON

57.6K

ON

OFF

115.2K

OFF

ON

230.4K

OFF

OFF

Disabled

Switch Position

1747-BSN Address

1

2

3

OFF

OFF

OFF

1

ON

OFF

OFF

2

OFF

ON

OFF

3

ON

ON

OFF

4

OFF

OFF

ON

5

ON

OFF

ON

6

OFF

ON

ON

7

ON

ON

ON

8

Note:

Switch position 4 is not used.