Rockwell Automation 1747-BSN Backup Scanner Module User Manual

Page 14

Advertising
background image

14

Backup Scanner Module

Publication 1747-5.38

Figure 7

Terminal Pinout

Use Belden™ 9463 cable when wiring the module.

Terminal screws accept a maximum of two #14 AWG (2mm

2

) wires. Tighten

terminal screws only tight enough to immobilize wires. Maximum torque on
terminal screws is 0.9 Nm (8 in-lbs.).

For Remote I/O Installations

1. To ensure a proper earth ground of the cable shield, follow these steps:

2. Strip back enough of the RIO cable to expose enough shield drain wire to

reach a chassis mounting bracket.

3. Attach the ring terminal lug to the end of the shield drain wire.

4. Attach the ring terminal lug to the SLC chassis mounting bracket.

!

ATTENTION: To avoid cracking the terminal block, alternate the removal and
tightening of the slotted release screws. Maximum torque on the release screws
is 0.6 Nm (5.3 in-lbs.).

Important: The RIO cable shield must be grounded at the backup scanner end

only.

Release Screw

HSSL (Line 1 – Blue)

HSSL (Shield)

HSSL (Line 2 – Clear)

Release Screw

DH+ (Line 2) to CPU

DH+ (Shield) to CPU

DH+ (Line 1) to CPU

232 / 485 (COM) to CPU

232 / 485 (B) to CPU

232 / 485 (A) to CPU

LSL (Line 2 – Clear)

LSL (Shield)

LSL (Line 1 – Blue)

232 / 485 (A) to Link

232 / 485 (B) to Link

232 / 485 (COM) to Link

RIO / DH+ (Line 1) to Link

RIO / DH+ (Shield) to Link
RIO / DH+ (Line 2) to Link