Backup Scanner Module

Publication 1747-5.38

Switchover Conditions

The 1747-BSN module transfers control from the primary to the secondary
processor (switchover) if one of the following fault conditions occurs in the
primary system:

• power failure

• major fault in the processor

• 1747-BSN module fault

• primary processor mode change from Run to Program

Installation

Determining Power Requirements

The BSN module is powered through the backplane of the I/O chassis. Before
installation, make sure that your modular SLC power supply has adequate reserve
capacity. The BSN module requires 800 mA at 5V.

Note:

In order for switchover to occur, both primary and
secondary modules must be working without faults prior
to the event that triggers the switchover.

!

ATTENTION: Disconnect system power before attempting to install, remove, or
wire the module.

Important: Use separate power sources for the primary and secondary

processors to protect against interruptions and incoming power
failures.