Status LEDs

The table below describes the six LEDs located on the module’s front panel. To
ensure that they are operating correctly, all LEDs are illuminated during power-up.

High-Speed Serial Link (HSSL)

The high-speed serial link supports communication between the primary and
secondary backup scanner modules. The baud rate is 2M baud, and the link
supports a distance of up to 4.5 m (15 feet).

The HSSL also transfers a limited number of SLC 500 data table files from the
primary to the secondary processor. The data table transfer is controlled by an
application program in the processor.

LED

Definition

Status and Color

Indication

PRI

Primary

Steady Green

The module is in the primary mode.

SEC

Secondary

Steady Amber

The module is in the secondary mode.

RIO

RIO Communication

Steady Green

The RIO link is working properly.

Flashing Green

A remote device is not configured or
connected correctly, or is faulted.

Flashing Red

The RIO link has a fault. The scanner is
connected incorrectly, or all devices are
configured improperly, have no power,
or are faulted.

Steady Red

There is a configuration error.

Off

The communication channel is not
configured as RIO.

ERR

Backup Module
Error

Flashing Red

The module is not ready for switchover.

Off

The module is ready for switchover.

HSSL

High Speed Serial
Link Communication

Flashing Green

The link is operating with no errors.

Off

A communications error has been
detected on the HSSL.

FLT

Fault

Steady Red

A hardware fault has occurred.

Flashing Red

The module is not configured properly.