Communicating to a remote data highway plus, Addressing from data highway plus chapter 5 – Rockwell Automation 1779-KP5_KP5R ORD.1779-5.3 User Manual

Page 51

Advertising
background image

Addressing from Data Highway Plus

Chapter 5

5Ć9

words from Memory Location N100:0 of the remote PLC-5 and stores
them in Memory Location N100:0 in the initiating PLC-5.

MESSAGE INSTRUCTION DATA ENTRY FOR CONTROL BLOCK N13:0

Read/Write: READ
PLC-5 Data Table Address:

Press a key to change a parameter or <RETURN> to accept parameters.
[

Program No Forces No Edits PLC-5/15 ADDR 20

READ/
WRITE

F1

PLC-5
ADDRESS

F2

SIZE IN
ELEMENTS

F3

LOCAL/
REMOTE

F4

REMOTE
STATION

F5

LINK
ID

F6

Remote Station:
Link ID:
Remote Link Type:

Size in Elements:
Local/Remote:

Local Node Address:
Processor Type:
Destination Data Table Address:

N100:0
1000
REMOTE
Node = 055 User = 013
00
DATA HIGHWAY II
50
PLC-5
N100:0

REMOTE
LINK

F7

LOCAL
NODE

F8

PROC.
TYPE

F9

DESTIN
ADDR

F10

BLOCK SIZE = 11 WORDS

There are two ways to communicate to a remote Data Highway Plus link:

Using a Data Highway II Link Number
Using a Data Highway Plus Link Number

The following sections show these two methods.

Using a Data Highway II Link Number

This method limits you to addressing a total of 15 nodes (02 through
20 octal) on a Data Highway Plus link, but it is also easier to implement.

Important: The address of the initiating Data Highway Plus node must
be between 02 and 20 (octal) so that the reply message can be returned.
The address of the initiating Data Highway Plus node must be between 02
and 20 (octal) so that the reply message can be returned.

Figure 5.4 shows an example configuration using a remote Data Highway
Plus link.

Communicating to a Remote

Data Highway Plus