Rockwell Automation 1734-OA4, Series C POINT I/O 120/220V AC Output Module Installation Instructions User Manual

Page 17

Advertising
background image

POINT I/O 120/220V AC Output Module 17

Publication 1734-IN009E-EN-E - March 2013

Indicator Status for Modules

Status

Description

Recommended Action

Module status

Off

No power applied to device.

Apply power to device.

Green

Device operating normally.

None.

Flashing green

Device needs commissioning
due to missing, incomplete, or
incorrect configuration.

Configure device properly.

Flashing red

Recoverable fault.

1. Cycle power to device.

2. If condition persists, replace
device.

Red

Unrecoverable fault – may
require device replacement.

Replace device.

Flashing red/green Device is in self-test mode.

None.

Network status Off

Device is not online:

- Device has not completed
dup_MAC-id test.

- Device not powered – check
module status indicator.

Apply power to device, wait for
MAC_id to complete and correct
as needed.

Flashing green

Device is online but has no
connections in the established
state.

None – device is in Idle or
Program mode.

Green

Device is online and has
connections in the established
state.

None.

Flashing red

One or more I/O connections are
in timed-out state.

Check for I/O module failure and
correct as needed.

Red

Critical link failure – failed
communication device. Device
detected error that prevents it
from communicating on the
network.

Verify that adapter and terminal
bases are properly installed and
reinstall as needed.

Flashing red/green Communication faulted device –

the device has detected a
network access error and is in
communication faulted state.
Device has received and
accepted an Identity
Communication Faulted Request
– long protocol message.

Verify that adapter is properly
installed and reinstall as
needed.

I/O status

Off

All outputs inactive.

None.

Yellow

One or more outputs are active
and under control.

None.