Thermal dissipation, max

1734-OA2 – 6.8 BTU @ @ 264V AC
1734-OA4 – 11.9 BTU @ @ 264V AC

Isolation voltage

240V (continuous), Reinforced Insulation
Type tested @ 3250V DC for 60 s, field-side to system

External AC power supply
voltage, nom

120/220V DC @ 60 Hz

External AC power supply
voltage range

85...264V DC @ 27...63 Hz

Dimensions, approx., HxWxD

56.0 x 12.0 x 75.5 mm

(2.21 x 0.47 x 2.97 in.)

Wiring category

(1)

1 – on signal ports

Wire size

Determined by installed terminal block

Weight, approx.

30.9 g (0.068 lb)

Pilot duty rating

DC 14 pilot duty

North American temp code

T4

IEC temp code

T4

Enclosure type rating

None (open-style)

Keyswitch position

8

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-IN041

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...55 °C (-4...131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal
Shock):
-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):

5...95% noncondensing

General Specifications