POINT I/O Output Module 11

Publication 1734-IN018C-EN-E - April 2013

Communicate with the Module

I/O messages are sent to (consumed) and received from (produced) the POINT I/O
modules. These messages are mapped onto the processor’s memory. This POINT I/O
output module consumes 1 byte of I/O data (scanner Tx).

Default Data Map for the 1734-OB2 Output Module

Message size: 1 Byte

7

6

5

4

3

2

1

0

Consumes (scanner Tx)

Not used

Ch1

Ch0

Channel state

Where: 0 = Off, 1 = On

Default Data Map for 1734-OB4

Message size: 1 Byte

7

6

5

4

3

2

1

0

Consumes (scanner Tx)

Not used

Ch3

Ch2

Ch1

Ch0

Channel state

Where: 0 = Off, 1 = On

Default Data Map for 1734-OB8

Message size: 1 Byte

7

6

5

4

3

2

1

0

Consumes (scanner Tx)

Ch7

Ch6

Ch5

Ch4

Ch3

Ch2

Ch1

Ch0

Channel state

Where: 0 = Off, 1 = On