General specifications – Rockwell Automation 1734-OB2_OB4_OB8, Series C POINT I/O Output Module Installation Instructions User Manual

Page 18

Advertising
background image

18 POINT I/O Output Module

Publication 1734-IN018C-EN-E - April 2013

OFF-state leakage, max

0.5 mA

Output signal delay, max

(1)

OFF to ON

ON to OFF

0.1 ms

0.1 ms

Output current rating

1734-OB2 – 1.0 A per output, 2.0 A max per module
1734-OB4, 1734-OB8 – 1.0 A per output, not to exceed 3.0 A max
per module

Surge current

2 A for 10 ms, repeatable every 3 s

Field wiring terminations

1734-OB2
0 – Output 0

1 – Output 1

2 – Output 0

3 – Output 1

4 – Common

5 – Common

6 – Supply

7 – Supply

1734-OB4
0 – Output 0

1 – Output 1

2 – Output 2

3 – Output 3

4 – Common

5 – Common

6 – Common

7 – Common

1734-OB8
0 – Output 0

1 – Output 1

2 – Output 2

3 – Output 3

4 – Output 4

5 – Output 5

6 – Output 6

7 – Output 7

(1)

Off–on delay is time from a valid output “On” signal to output energization. On–off delay is time from a valid output
“off” signal to output de-energization.

General Specifications

Attribute

Value

Terminal base screw torque

0.8 Nm (7 lb-in.)

Indicators

1734-OB2

2 yellow – output status

2 green/red – module/network status
1734-OB4

4 yellow – output status

2 green/red – module/network status
1734-OB8

8 yellow – output status

2 green/red – module/network status

Module location

1734-TB or 1734-TBS wiring base assembly

POINTBus current, max @ 5V DC

75 mA

Power dissipation, max @ 28.8V DC

1734-OB2 – 0.8 W
1734-OB4 – 1.2 W
1734-OB8 – 2.0 W

Thermal dissipation, max @ 28.8V DC

1734-OB2 – 2.7 BTU/hr
1734-OB4 – 4.1 BTU/hr
1734-OB8 – 6.8 BTU/hr

POINT I/O Output Module – 1734-OB2, 1734-OB4, 1734-OB8

Attribute

Value