POINT I/O Output Module 19

Publication 1734-IN018C-EN-E - April 2013

Isolation voltage

50V (continuous), Reinforced Insulation Type
Type tested @ 2500V DC for 60 s, field-side to system

External DC power supply voltage, nom

24V DC

External DC power voltage range

10...28.8V DC

External DC power supply current

1734-OB2 – 8 mA
1734-OB4 – 16 mA
1734-OB8 – 32 mA

Dimensions, HxWxD, approx.

56.0 x 12.0 x 75.5 mm

(2.21 x 0.47 x 2.97 in.)

Wiring category

(1)

2 – on signal ports

Wire size

Determined by installed terminal block

Weight, approx.

1734-OB2 – 32.60 g (1.15 oz)
1734-OB4 – 33.17 g (1.17 oz)
1734-OB8 – 35.4 g (1.25 oz)

North American Temp Code

1734-OB2 – T4A
1734-OB4 – T4A
1734-OB8 – T4

IEC Temp Code

T4

(1)

Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring
and Grounding Guidelines, publication

1770-IN041

.

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...55 °C (-4...131 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40...85 °C (-40...185 °F)

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5...95% non-condensing

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10...500 Hz

General Specifications