Specifications – Rockwell Automation 1734-OB2_OB4_OB8, Series C POINT I/O Output Module Installation Instructions User Manual

Page 17

Advertising
background image

POINT I/O Output Module 17

Publication 1734-IN018C-EN-E - April 2013

Specifications

Indicator Status for Modules

Status

Description

Module status

Off

No power applied to device.

Green

Device operating normally.

Flashing green

Device needs commissioning due to missing, incomplete, or
incorrect configuration.

Flashing red

Recoverable fault.

Red

Unrecoverable fault – may require device replacement.

Flashing red/green Device is in self-test mode.

Network status Off

Device is not online:

- Device has not completed dup_MAC-id test.

- Device not powered – check module status indicator.

Flashing green

Device is online but has no connections in the established state.

Green

Device is online and has connections in the established state.

Flashing red

One or more I/O connections are in timed-out state.

Red

Critical link failure – failed communication device. Device detected
error that prevents it from communicating on the network.

Flashing red/green Communication faulted device – the device has detected a

network access error and is in communication faulted state. Device
has received and accepted an Identity Communication Faulted
Request – long protocol message.

I/O status

Off

All outputs inactive.

Yellow

One or more outputs is active and under control.

POINT I/O Output Module – 1734-OB2, 1734-OB4, 1734-OB8

Attribute

Value

Outputs per module

1734-OB2 – 2 (1 group of 2) non-isolated, sourcing
1734-OB4 – 4 (1 group of 4) non-isolated, sourcing
1734-OB8 – 8 (1 group of 8) non-isolated, sourcing

ON-state voltage range, min

10V DC

ON-state voltage range, nom

24V DC

ON-state voltage range, max

28.8V DC

ON-state voltage drop, max

0.2V DC

ON-state current, min per channel

1.0 mA

OFF-state voltage, max

28.8V DC

Advertising