Connect the Power Supply

Keep the following in mind when connecting the power supply to the switch:

Use the supplied 3-pole, 5.08 mm (0.20 in.) pitch terminal block to connect the
power wire.

Use wires of 2.5 …

0.75 mm

(14…18 AWG).

Grounding resistance must be <2.5

.

WARNING: Before performing any of the following procedures, make sure power is removed from
the DC circuit or the area is nonhazardous before proceeding.

ATTENTION: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered
from a source compliant with the safety extra low voltage (SELV) or protected extra low voltage
(PELV). To comply with UL restrictions, this equipment must be powered from a source compliant
with Class 2 or Limited Voltage/Current.

Power Supply Pinouts

Pin

For DC Wiring

For AC Wiring

1

PWR: +

PWR: L

2

PWR: -

PWR: N

3

Functional Ground (FE)

Functional Ground (FE)

N

L

PWR

1 2 3

32315-M