6 Stratix 2000 Ethernet Unmanaged Switch

Rockwell Automation Publication 1783-IN010A-EN-P - June 2013

To prevent the switch from overheating, observe the following minimum

clearances:

Top and bottom: 50.80 mm (2 in.)

Sides: 50.80 mm (2 in.)

Front: 63.50 mm (2.50 in.)

Temperature surrounding the unit must not exceed 140 °F (60 °C).

Install the Switch

Perform these procedures to install the switch:

Install the Switch on a DIN Rail on page 6

Remove the Switch from a DIN Rail on page 8

Wire the Switch on page 8

Connect the Power Supply on page 10

Ground the Switch on page 12

Apply Power to the Switch on page 13

Install the Switch on a DIN Rail

Follow these procedures to install the switch on a DIN rail.

ATTENTION: When using DIN rail mounting, additional grounding is also accomplished through
the DIN rail to chassis ground. Use zinc-plated yellow-chromate steel DIN rail to assist in proper
grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode,
oxidize, or are poor conductors, can impede proper grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.).