Troubleshoot with the indicators – Rockwell Automation 1738-XXXX ArmorPoint 24V dc Output Modules, Series A User Manual

Page 10

Advertising
background image

Publication 1738-IN001C-EN-E - June 2005

10 ArmorPoint 24V dc Output Modules, Series A

Troubleshoot with

the Indicators

Indication

Probable Cause

Module Status

Off

No power applied to device

Green

Device operating normally

Flashing Green

Device needs commissioning due to missing, incomplete, or
incorrect configuration

Flashing Red

Recoverable fault

Red

Unrecoverable fault - may require device replacement

Flashing Red/Green

Device is in self-test

Indication

Probable Cause

Network Status

Off

Device is not on line:

- Device has not completed dup_MAC-id test.

- Device not powered - check module status indicator.

Flashing Green

Device is on line but has no connections in the established state.

Green

Device is on line and has connections in the established state.

Flashing Red

One or more I/O connections in timed-out state.

Red

Critical link failure - failed communication device. Device detected
error that prevents it from communicating on the network.

Flashing Red/Green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.

MOD

NET

0

1

2

3

4

5

6

7

1738-OB8EM12/A

24V dc Out

0

1

2

3

4

5

6

7

Module Status Indicator

43676

1738-OB8EM12

Network Status Indicator

I/O Status Indicators

Advertising