12 ArmorPoint 24V dc Output Modules, Series A

General Specifications (cont)

LED Indicators

2, 4, or 8 yellow/red output status, logic side

1 green/red network status, logic side

1 green/red module status, logic side

Output Delay Time, OFF to ON, Max.

1

0.1 ms

Output Delay Time, ON to OFF, Max.

1

0.1 ms

Output Point Density

2, 4, 8

PointBus Current, Max.

75 mA @ 5V dc

Power Dissipation, Max.

1738-OB2E - 0.8W @ 28.8V dc

1738-OB2EP - 3.4W @ 28.8V dc

1738-OB4E - 1.2W @ 28.8V dc

1738-OV4E - 2.9W @ 28.8V dc

1738-OB8E - 2.0W @ 28.8V dc

Thermal Dissipation, Max.

1738-OB2E - 2.7 BTU/hr. @ 28.8V dc

1738-OB2EP - 11.6 BTU/hr. @ 28.8V dc

1738-OB4E - 4.1 BTU/hr. @ 28.8V dc

1738-OV4E - 9.9 BTU/hr. @ 28.8V dc

1738-OB8E - 6.8 BTU/hr. @ 28.8V dc

Weight, Imperial

0.64 lb

Weigh, Metric

0.29 kg

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20 … 60 °C (-4 … 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 … 85 °C (-40 … 185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat):

5-95% non-condensing

Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock):

Operating 30 g

Non-operating 50 g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10-500 Hz

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 30 MHz to 2000 MHz

10V/m with 200 Hz 50% Pulse 100% AM at 900 Mhz

10V/m with 200 Hz 50% Pulse 100% AM at 1890 Mhz

EFT/B Immunity

IEC 61000-4-4:

±3 kV at 5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:

10Vrms with 1 kHz sine-wave 80% AM from 150 kHz … 80 MHz

Emissions

CSPR 11:

Group 1, Class A