1738-ob8em23, Communicate with your module, Default data map for the armorpoint output modules – Rockwell Automation 1738-XXXX ArmorPoint 24V dc Output Modules, Series A User Manual

Page 8

Advertising
background image

Publication 1738-IN001C-EN-E - June 2005

8 ArmorPoint 24V dc Output Modules, Series A

1738-OB8EM23

Communicate with

Your Module

I/O messages are sent to (consumed) and received from (produced)
the ArmorPoint I/O modules. Messages are mapped into the
processor’s memory. ArmorPoint I/O output modules produce 1 byte
of input data (scanner Rx - status). They consume 1 byte of I/O data
(scanner Tx).

Default Data Map for the ArmorPoint Output Modules

1738-OB2EM12 and 1738-OB2EPM12

Message size: 1 Byte

ATTENTION

Make sure all connectors and caps are securely
tightened to properly seal the connections against
leaks and maintain IP67 requirements.

3

4

5

6

7

8

9

10

11

12

2

1

43681

(view into connector)

Pin 1 -Output 0

Pin 7 - Output 6

Pin 2 -Output 1

Pin 8 - Output 7

Pin 3 -Output 2

Pin 9 - Return (Com)

Pin 4 -Output 3

Pin 10 - Return (Com)

Pin 5 -Output 4

Pin 11 - 24V dc

Pin 6 -Output 5

Pin 12 - Chassis

7

6

5

4

3

2

1

0

Produces

(scanner Rx)

Not Used

Ch1

Ch0

Channel status

Consumes

(scanner Tx)

Not Used

Ch1

Ch0

Output state

Where: Channel status 0 = no error, 1 = error; Output state 0 = off, 1 = on