156 Specifications

MicroLogix 1100 DC Input Power Requirements for 1763-L16BBB Unit

ESD immunity

EN 61000-4-2
4 kV contact, 8 kV air, 4 kV indirect

Radiated RF immunity

EN 61000-4-3
10V/m, 26…1000 MHz (alternatively, 80…1000 MHz),
80% amplitude modulation, +900 MHz keyed carrier

Fast transient immunity

EN 61000-4-4
2 kV, 5 kHz
communications cable such as EtherNet, RS-232, and RS-485: 1 kV, 5 kHz

Surge transient immunity

EN 61000-4-5
Unshielded communications cable: 2 kV CM (common mode), 1 kV DM (differential mode)
Shielded communications cable: 1 kV galvanic gun
I/O: 2 kV CM (common mode), 1 kV DM (differential mode)
AC Power Supply Input: 4 kV CM (common mode), 2 kV DM (differential mode)
DC Power Supply Input: 500V CM (common mode), 500V DM (differential mode)
AC/DC Auxiliary Output: 500V CM (common mode), 500V DM (differential mode)

Conducted RF immunity

EN 61000-4-6
10V, 150 kHz…80 MHz

Conducted emissions

EN 55011
AC Power Supply Input: 150 kHz…30 MHz

Radiated emissions

EN 55011
30…1000 MHz

Line related tests

EN 61000-4-11
AC Power Supply Input:
voltage drop: -30% for 10 ms, -60% for 100 ms
voltage interrupt: at voltage greater than -95% for 5 sec.
voltage fluctuation: +10% for 15 minutes, -10% for 15 minutes
DC Power Supply Input:
voltage fluctuation: +20% for 15 minutes, -20% for 15 minutes

General Specifications

Description

1763-

L16AWA

L16BWA

L16BBB

L16DWD

4

8

12

16

20

28

21

14

7

1763-L16BBB and 1763-L16DWD Typical Power Requirements