Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 160

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

158 Specifications

Analog Input Specifications

Description

1763-L16AWA, -L16BWA, -L16BBB, -L16DWD

Voltage input range

0…10.0V DC - 1 LSB

Type of data

10-bit unsigned integer

Input coding (0...10.0V DC - 1 LSB)

0…+1,023

Voltage input impedance

210 k

Ω

Input resolution

10 bit

Non-linearity

±1.0% of full scale

Overall accuracy
-20…65 °C (-4…149 °F)

±1.0% of full scale

Voltage input overvoltage protection

10.5V DC

Field wiring to logic isolation

Non-isolated with logic

Output Specifications - General

Description

1763-

L16AWA, L16BWA, L16DWD

L16BBB

Relay and FET Outputs

Maximum controlled load

1,440 VA

1,440 VA

Maximum continuous current

Current per group common

(1)

5 A/3 A

5 A/3 A

Current per controller

at 150V max

For UL 508, 30 A or total of per-point loads, whichever is less
For UL 1604, 18 A or total of per-point loads, whichever is less

at 240V max

For UL 508, 20 A or total of per-point loads, whichever is less
For UL 1604, 18 A or total of per-point loads, whichever is less

Relay Outputs

Turn on time/Turn off time

10 ms (minimum)

(2)

Relay life - Electrical

For Hazardous Locations Applications (Class I, Division 2, Groups A, B, C, D):
150 x 10

3

operations min. (at 3 A, 30V DC);

370 x 10

3

operations min. (at 3 A, 250V AC);

For Ordinary (Non-Hazardous) Locations only:
50 x 10

3

operations min. (at 5 A, 30V DC);

170 x 10

3

operations min. (at 5 A, 250V AC);

Load current

10 mA (min.)

(1) 5A for UL 508

3A for UL 1604, Class 1, Division 2, Hazardous Locations, Groups A, B, C, D

(2) scan time dependent