Connecting the AIC+

You can connect a MicroLogix 1100 controller to a DH-485 network via
Channel 0 directly without using an optical isolator, such as AIC+, catalog
number 1761-NET-AIC, because Channel 0 is isolated. However, you need to
use an AIC+ to connect your PC or other MicroLogix Family products, such
as MicroLogix 1200, to a DH-485 network.

The following figure shows the external wiring connections and specifications
of the AIC+.

For additional information on connecting the AIC+, refer to the Advanced
Interface Converter (AIC+) User Manual, publication 1761-UM00.

Item

Description

1

Port 1 - DB-9 RS-232, DTE

2

Port 2 - mini-DIN 8 RS-232 DTE

3

Port 3 - RS-485 Phoenix plug

4

DC Power Source selector switch
(cable = port 2 power source,
external = external power source connected to item 5)

5

Terminals for external 24V DC power supply and chassis ground

AIC+ Advanced Interface Converter
(1761-NET-AIC)

3

2

4

5

1